What is the value of cos 1710

COMFORT CHILLERS. AIR-COOLED CHILLERS WITH SCREW COMPRESSORS, FROM 140 TO 1710 kw R513A

Transcript

1 COMFORT CHILLERS AIR-COOLED CHILLERS WITH SCREW COMPRESSORS, FROM 140 TO 1710 kw R513A

2 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS THE ENVIRONMENTALLY FRIENDLY SOLUTION FOR PERFECT COMFORT In modern multi-purpose buildings, shopping centers, business premises or health care facilities, more and more comfort is required with simultaneously reduced operating costs and the smallest possible ecological footprint. The sustainability-oriented design of the FX-G05 series achieves the highest efficiency targets demanded by modern projects and offers an environmentally friendly approach for every type of air conditioning. a Hotels a Shopping centers a Office buildings a Museums COMFORT APPLICATIONS a Training centers a Sports halls a Bank buildings a Public facilities SOLID EVEN UNDER EXTREME CONDITIONS FAST AND EASY INSTALLATION COMPREHENSIVE CONFIGURABILITY The FX-G05 series can be operated in all climate zones between 20 C and +57 C. Thanks to the highly resistant coating of the heat exchangers, it can withstand even the toughest conditions in the marine or industrial sector. The integrated hydraulic modules allow quick and easy assembly. The pumps with variable speed are used optimally, the water volume flow is regulated intelligently. This saves time during commissioning and enables significant energy savings. Thanks to a variety of configurations and accessories, the FX-G05 series can be easily integrated into increasingly complex building systems. COMPLETE PROGRAM OF CHILLED WATER SETS Low GWP from 140 to 1710 kw FX-G units with one compressor E CA Very high efficiency High efficiency EER: 3.16 EER: 3.03 SEER: 4.32 SEER: 4.22 FX-G Units with two or three compressors K standard efficiency EER: 2.74 SEER: 4, cooling capacity [kw] MODELS WITH SOUND INSULATION Average values ​​(EN 14511) of FX-G HEAT RECOVERY CONFIGURATIONS - SL compact unit Super low noise unit with standard sound insulation. Unit with sound-insulated compressor housing (opt. 2301). Device with noise reducer kit for noise reduction (opt. 2315). Highest level of noise reduction; Noise emissions are 10 to 12 db (a) lower without reducing the performance of the device. Compact series 2 db (a) 7 db (a) 12 db (a) - D R compact unit Partly Approx. 20% of the unit output is recovered with the help of a heat recovery desuperheater on the hot gas line. Complete heat recovery device for generating cold water. A refrigerant / water heat exchanger specially designed for this purpose ensures that all of the condenser heat is recovered. Compact series 60 C 55 C 60 C With HT kit 02/03

3 ALL-ROUND SUSTAINABILITY The FX-G05 series is the result of the far-reaching sustainability approach of Mitsubishi Electric Hydronics & IT Cooling Systems. With increasing concerns about the effects of chillers and heat pumps on global warming, new regulatory measures are being pushed to make them more efficient and have the smallest possible carbon footprint. R513A Today, a holistic approach is the only way to effectively reduce the TEWI value (Total Equivalent Warming Impact). 02/03 Mitsubishi Electric Hydronics & IT Cooling Systems is fully committed to creating a more environmentally friendly future and has therefore developed the FX-G05 series, a complete range of water chillers with reduced environmental impact, optimized for the refrigerant R513A. By combining first-class annual efficiency and the use of a refrigerant with a low global warming potential, the FX-G05 series counteracts direct and indirect global warming (due to primary energy consumption). It is therefore an ideal choice for every new, future-oriented cooling system. R513A LOW GWP VALUE 56% GWP compared to R134a NON-FLAMMABLE Safety class A1 COMPARISON OF DIFFERENT REFRIGERANTS Refrigerant GWP * Flammability ** Refrigerant GWP * Flammability ** R410A R32 SCROLL NON-flammable NON-flammable NON-flammable SCa R134 R134 NON-flammable NON-flammable R134 EU regulation on fluorinated greenhouse gases and the Kigali amendment to the Montreal Protocol urge the industry to develop new, environmentally friendly refrigerants with a reduced greenhouse effect. Unfortunately, the majority of low GWP refrigerants have another critical problem of increased flammability. R454B R452B * IPCC AR4 ** ASHRAE 34 - ISO 817 HARD flammable HARD flammable 1234ze 1234yf 7 4 HARD flammable HARD flammable The refrigerant R513A selected for the FX-G05 series is an exception: It offers a GWP reduction of 56% compared to R134a and is at the same time completely non-toxic and non-flammable (ASHRAE 34 class A1, ISO 817). IN-DEPTH KNOW-HOW EXCELLENT Thanks to the experience with thousands of devices installed worldwide (since 2003), the air-cooled chillers from Climaveneta are now in their third generation: the FX-G05 series. Factors of this success story are the best manufacturing quality, proven reliability and complete configurability. The devices of the FX-G05 series combine extensive know-how with state-of-the-art technology in order to offer you maximum added value. Devices of the FX-G05 series offer tailor-made application design for individual projects: fully configurable models in different variants with accessories. Thanks to sophisticated technical solutions and precise construction, the FX-G05 series enables maximum performance in full load and excellent efficiency in partial load operation in every configuration. In this way, energy consumption and operating costs of air conditioning systems in private and business areas can be reduced.

4 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS TECHNICAL EQUIPMENT CONTROL W3000 TE Control software developed in-house. 4 Efficient, reliable operation under all conditions 4 Connectivity with common building control protocols (opt.) KIPlink USER INTERFACE Innovative WLAN interface for simple, improved device management. Communication based on WLAN technology (no internet connection required) An exclusive product from Mitsubishi Electric Hydronics & IT Cooling Systems Hardware meets industrial requirements, temperature range 20 C to +65 C Microchannel condensers New generation of microchannel condensers made of all-aluminum, ideally positioned in one V-block structure to optimize airflow and heat transfer. 4 Up to 30% less refrigerant required than with conventional Cu / Al heat exchangers 4 Long-life alloy (LLA) for higher corrosion resistance and longer service life 4 Protective coating for the toughest conditions in the marine sector or in industry available (opt.) CSC screw compressor VARIABLE PRIMARY FLOW Integrated pump group (opt.) Factory-assembled pumps and pre-piped hydraulic components guarantee minimal work, time and costs for on-site assembly. Double rotor screw compressor, specially tailored to the requirements of Mitsubishi Electric Hydronics & IT Cooling Systems and available exclusively. 4 Pumps with fixed or variable speed, available with low or high head. 4 Electronic control of the primary volume flow for even pressure or constant temperature 04/05

5 The FX-G05 series combines advanced technology and know-how in customer-specific packages for improvements in design, specification, assembly and during operation Variable fan speed High-performance axial fan with transformer for speed adjustment. 4 Precise control of the air volume flow, reduced energy consumption and lower sound level in partial load operation 4 Completely independent air volume flows for each refrigerant circuit 4 EC fan with a protected algorithm for energy saving and for operation at very low ambient temperatures (opt.) R513A refrigerant with low global warming potential New generation refrigerant with reduced greenhouse effect. Not flammable. Reduced GWP value R513A GWP100 years = 572 (R134a GWP100 years = 1300) GWP values ​​according to IPCC AR5 Non-toxic, non-flammable ASHRAE 34 Class A1, ISO 817 Favorable physical properties Provides the same cooling capacity as R134a Same operating pressures as R134a 04/05 In In accordance with the usual building regulations No special equipment required No flammability risk assessment required No additional costs In line with the goals of the ErP Directive No future refrigerant conversions required Shell and tube evaporator Shell and tube evaporator without bends, completely developed by Mitsubishi Electric Hydronics & IT Cooling Systems. 4 Internally finned copper pipes for improved heat exchange 4 Low pressure losses 4 Increased protection against ice formation Brazed plate heat exchangers for small sizes (<200 kw) Innovative geometry in the interior Thanks to their specific design, which aims to optimize the internal volume for partial load operation, the CSC compressors offer outstanding performance under a wide variety of operating conditions. Optimized oil lubrication The oil circuit is calibrated with the help of a special oil management valve, which significantly increases the compressor efficiency in partial load operation. Long service life. B. Carbon steel bearings with a guaranteed lifetime of operating hours. EER [-] 5.50 5.00 4.50 4.00 3.50 3.00 2.50 + 15.5% chillers with CSC screw compressors + 11.7% + 8.5% cooling capacity (%) + 1.6% chillers with traditional screw compressors The diagram shows the efficiency of the chiller with different output and air temperature.

6 ifxq2 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS ESSENTIAL FUNCTIONS FOR ALL REQUIREMENTS OF YOUR SYSTEM W3000 TE control unit and the innovative KIPlink interface The FX-G05 series is controlled by the W3000 TE control unit. W3000 TE offers the most modern functions and algorithms as well as protected setting options. In this way, faster adaptation behavior is guaranteed in all operating modes with the most varied of dynamics. The device can be operated directly via the innovative KIPlink interface. Since the interface uses a local WLAN, you can do without the keyboard with KIPlink and work directly on the system via a mobile device (smartphone, tablet, notebook). Easier on-site operation Graphics and trends in real time Data logger function Walk around the system during maintenance and check every component. View and change all parameters via easy-to-understand screen views and special tool tips. There are special help messages for resetting alarms and for troubleshooting. Master Unit How to access the device with KIPlink You can get direct access to the W3000 TE control unit by using the QR code on the front of the FX-G05 device to scan. Check the current status of the compressors, heat exchangers, cooling circuits or pumps. Evaluate real-time graphics and trends of the most important operating parameters. LED switch View the history of events and use the filter for easy search. To facilitate fault diagnosis, data and graphics are saved for a period of 20 minutes from 10 minutes before the fault occurs. Download all data to create a detailed analysis. The three-colored LED button on the control cabinet is used to switch it on and off and shows the general status of the system without the need to use a mobile device. In addition to (opt. 1442, 1444) or as a replacement (opt. 6194, 6195) for KIPlink, the FX-G05 device can be equipped with a color 7 "touchscreen display or a keyboard with a large display and LED symbols. In this case the LED switch is not used. A remote display is also available (opt. C, C, C, C) Factory acceptance test (FAT) Convince yourself of the performance of your device under the toughest conditions of the installation Factory acceptance test of the performance As an additional service, we offer you a factory acceptance test, which means: Even before your chiller leaves the factory, you as the customer have the opportunity to personally convince yourself of how the system behaves under certain conditions You can choose between different test options in our modern, sophisticated test rooms: 4 performance of your device 4 noise emissions under real conditions 16 sizes 4 performance of the system in full and partial load operation CA Effiz ienz 4 Operation of the system at low outside temperatures SL version 4 Measurement of the time until the quick restart 06/07

7 06/07 Hydraulic modules and volume flow control Devices of the FX-G05 series can be equipped with a factory-installed pump group, which reduces space, time and costs for hydraulic and electrical installation, or simply with digital and analog outputs for controlling external pumps the internal control logic. Pumps in block design from Grundfos. Coupling of main seals made of SiC / SiC (silicon carbide), extremely resistant to wear and abrasion particles. EPDM bellows seal prevents the risk of deposits (e.g. rust) on the shaft. Pull-out construction: The drive head can be pulled out for maintenance without removing the pump housing from the piping. In-line or block pumps are used depending on the dimensions and performance. Factory-fitted pump group 2 pumps (operation / standby) with low or high delivery head (available with approx. 100 or 200 kpa). 1 pump available for units with one compressor. Fixed-speed pumps Variable-speed pumps 1 Standard pump head 2-pole: Opt Large head 2-pole: Opt Standard pump head 2-pole: Opt. 4711/4-pole: Opt Large head 2-pole: Opt. 4712 / 4- pole: Opt Pump standard delivery head 2-pole: Opt high delivery head 2-pole: Opt Pumps standard delivery head 2-pole: Opt. 4722/4-pole: Opt Large delivery head 2-pole: Opt. 4723/4-pole: Opt Connections for external Pump groups Special end devices are available for controlling one or two external pumps at fixed or variable speed. On / Off signal 1 Pump Opt Pump Opt Modulating signal 1 Pump Opt Pump Opt VARIABLE PRIMARY FLOW VPF control logic The VPF logic (variable primary volume flow) regulates the pump speed according to the heat load. At the same time, it has a positive effect on the device's heat control algorithms so that they can be optimized for operation with variable volume flow. Maximum energy savings, stable operation and high reliability are always guaranteed. VPF: constant ΔP on the system side For systems that consist of only one primary circuit. Opt or 4865 for systems with only one device. Opt for systems with multiple devices. VPF.D: constant ΔT on the system side For systems with primary and secondary circuits that are separated by a hydraulic distributor circuit. Opt for systems with only one device. Opt for systems with multiple devices. For quick and easy commissioning, it is possible to set the pump speed directly from the device control (opt. 4862). Operating limits

8 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS ACCESSORIES EC fans EC fans (opt. 808): EC fans with brushless motors that adjust the speed if necessary to minimize energy consumption and noise emissions, especially in partial load operation (+1% for EER, + 5% with SEER). +5% SEER sound reduction Soundproofed compressor housing (opt. 2301): Housing made of painted sheet metal panels, lined with soundproofing insulation. Reduction of sound power: 2 db (a). Set for noise minimization (opt. 2315): The set includes fans with adapted speed control as well as sound insulation of the relevant components. Reduction of sound power: 7 db (a). Heat exchangers and coatings MICROCHANNEL CONDENSER Al normal (standard) Al epoxy coating (opt.876) 3120 h SWAAT test (ASTM G85-02 A3) Epoxy coating a UV-resistant Alkaline cleaning Rinsing with deionized water Epoxy treatment Final curing process Rinsing UV topcoat COPPER AND ALUMINUM LIQUID Cu / Al normal (opt. 879 ) Cu / Al coated lamellas (Opt. 894) Cu / Al high pressure spray coating (Opt. 895 / RFQ) Fin Guard Silver SB * Opt. 895 polyurethane resin with aluminum filler a3000 h ASTM B117 auv resistance excellent * Thermoguard PoluAl XT * RFQ polyurethane resin with aluminum filler a 4000 h ASTM B117 auv resistance excellent * Blygold Heresite P-413C * RFQ phenolic resin a 6000 h ASTM B117 a UV - Resistance good * Heresite Protective Coating, LLC. Cu / Cu tubes and lamellas (opt. 881) 08/09

9 08/09 ADDITIONAL ACCESSORIES Additional inputs 4 20 mA setpoint shift (Opt. 6161): change the setpoint via on-site 4 20 mA signal (analog input). Second setpoint (opt. 6162): switch between two fixed setpoints (digital input). Power limitation (opt. 6171): if necessary, briefly reduces the power of the systems (digital input). Electrical accessories Power factor correction of the compressors (opt. 3301): Capacitors for power factor correction are installed on the compressors in order to increase the cos phi of the device. Automatic circuit breakers for compressors (opt. 3411) or all important electrical consumers (opt. 3412): Automatic circuit breakers are provided for the electrical consumers instead of fuses. Soft starter (opt. 1511) or 3-phase soft starter (opt. 1513): eliminates the current peaks when the compressor is switched on and thus protects the motor winding from mechanical wear. Reduces the voltage drops when the device starts up. Connectivity Connection to the building management system: Interface module with serial card for the integration of BMS protocols: Modbus (opt. 4181) / LonWorks (opt. 4182) / BACnet MS / TP (opt. 4184) / BACnet over IP (opt. 4185). M-Net interface kit (opt. 4187): Interface module for integrating the device into the M-Net communication protocol developed by Mitsubishi Electric. Electricity meter Electricity meter with BMS determines the electrical power consumption of the device and transmits the values ​​to a BMS (Modbus RS485) Refrigerant circuit Double safety valves with gate valve (opt. 1961): One valve is separated from the refrigerant circuit while the other is in operation. The user can work on the shut-off valve (maintenance, replacement) without having to remove the refrigerant from the refrigeration circuit. Shut-off valve on the compressor suction side (opt. 1901): mounted on each compressor on the suction side. Simplifies maintenance work (shut-off valves on the pressure side are standard). Refrigerant leak detector Leak detector (opt. 3431): factory-fitted. Triggers an alarm in the event of a leak. Leak detector + compressor switch-off (opt. 3433): fitted at the factory. In the event of a leak, it triggers an alarm and stops the device. Hydraulic flow monitor (opt. 1801): protects the system if the water volume flow through the evaporator is outside the operating limits. Delta T> 8 C (opt. 2881): Evaporator for operation with low water volume flow. Flanged hydraulic connections (opt. 2911): grooved coupling with counter tube flanges. Structure of protective grille (opt. 2021): all-round metal grille to protect against the ingress of solid objects in rubber (opt. 2101) or vibration damper (opt. 2102): reduce vibrations in order to keep noise transmission as low as possible. Reinforcing bar packaging (opt. 1971): Steel angle to reinforce the system structure. Advisable for long haulage on trucks. Nylon packaging (opt. 9966): The FX-G05 device is covered with a protective cover made of nylon and provided with lifting eyes for loading into a truck. Container packaging (opt. 9979): The FX-G05 device is covered with a protective cover made of nylon, reinforced with reinforcing bars and provided with both lifting lugs and loading aids for bringing it into the container (metal slide, handlebar at the front).

10 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 140 to 396 kw. 2 values ​​according to the EN standard: Average sound pressure level at a distance of 10 m, for devices outdoors on a reflective surface; Non-binding value determined from the sound power. 4 Sound power, measured according to the ISO 9614 standard. 5 Sound power in cooling mode, outside. 6 Device with standard configuration and design, without optional accessories. 7 Nominal cooling capacity for cooling operation [REGULATION (EU) 2016/2281] 8 Annual coefficient of performance in cooling operation 9 annual efficiency factor The devices specified in this document contain fluorinated greenhouse gases R513A [GWP]. EUROVENT certified dates 10/11

11 10/11 R R513A COOLING SCREW VPF VAR. PRIM.

12 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 289 to 1710 kw. 2 values ​​according to the EN standard: Average sound pressure level at a distance of 10 m, for devices outdoors on a reflective surface; Non-binding value determined from the sound power. 4 Sound power, measured according to the ISO 9614 standard. 5 Sound power in cooling mode, outside. 6 Device with standard configuration and design, without optional accessories. 7 Nominal cooling capacity for cooling operation [REGULATION (EU) 2016/2281] 8 Annual coefficient of performance in cooling operation 9 annual efficiency factor The devices specified in this document contain fluorinated greenhouse gases R513A [GWP]. EUROVENT-certified dates 12/13

13 12/13 R R513A ENERGY CLASS COOLING SCREW VPF VAR. PRIM. FLOW SHELL & TUBES AXIAL FX-G05 / K Power supply V / ph / Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3 / 50 Cooling capacity (1) kw Total power consumption (1) kw 443.8 485.7 485.8 535.1 569.7 593.7 619.2 EER (1) kw / kw 2.792 2.683 2.884 2.768 2.715 2.786 2.762 ESEER (1st ) kw / kw 4.190 4.220 4.190 4.200 4.160 4.200 4.230 ONLY (EN14511 VALUE) cooling capacity (1) (2) kw EER (1) (2) kw / kw 2.760 2.650 2.850 2.730 2.690 2.750 2.730 ESEER (1) (2) kw / kw 4.030 4.040 4.030 4.030 4.020 4.040 4.050 EUROVENT class CDCCDCC Prated, c (7) kw SEER (7) (8) 4.10 4.10 4.12 4.11 4.10 4.12 4.12 Annual efficiency ηs ( 7) (9)% CONSUMER SIDE IN COOLING MODE Water flow rate (1) l / s 59.26 62.29 67.01 70.81 74.00 79.11 81.79 Pressure loss (1) kpa 46.9 51.8 45. 4 50.7 39.0 44.6 51.2 Number of compressors N Number of refrigeration circuits N Refrigerant charge kg Sound pressure (3) db (a) Sound power (4) (5) db (a) A (6) mm B (6) mm H (6) mm Operating weight (6) kg

14 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 289 to 1710 kw. (On) 35 C. 2 values ​​according to EN: 2013. Standard EN: Average mean sound pressure level Sound pressure level at a distance of 10 m, at a distance of 10 m; for devices for outdoors outdoors in outdoors reflective on reflective surface; from surface; the sound power on the basis of a calculated value that is not binding on the sound power level. 4 Sound power, non-binding according to value. Measured according to ISO 9614. 45 Sound power after in cooling mode, measurements outside. according to ISO device 5 sound power level with standard configuration in cooling mode, and design, outdoors. without optional accessories. 7 Nominal cooling capacity 6 System in standard configuration for cooling operation and [REGULATION version, without (EU) optional 2016/2281] accessories. 8 Annual performance factor 7 parameters calculated in cooling mode according to (REGULATION [EU] 2016/2281). 9 S-annual efficiency value 8 Seasonal energy efficiency value. The 9 devices, seasonally dependent, the room cooling specified in this energy efficiency document. are, contain fluorinated greenhouse gases plants included in R513A of this [GWP100 publication 631]. marked, EUROVENT-certified ones contain fluorinated greenhouse gas data of the type R513A (GWP). EUROVENT certified data

15 14/15 R R513A ENERGY CLASS COOLING SCREW VPF VAR. PRIM. FLOW SHELL & TUBES AXIAL FX-G05 / SL-K Power supply V / ph / Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400 / 3/50 Cooling capacity (1) kw Total power consumption (1) kw 451.2 478.6 494.5 531.6 563.4 607.6 635.5 EER (1) kw / kw 2.646 2.693 2.730 2.752 2.716 2.625 2.595 ESEER (1) kw / kw 4.180 4.220 4.180 4.200 4.160 4.170 4.180 ONLY (EN14511 VALUE) cooling capacity (1) (2) kw EER (1) (2) kw / kw 2.620 2.660 2.700 2.720 2.690 2.600 2.570 ESEER (1) (2) kw / kw 4.020 4.040 4.030 4.030 4.030 4.030 4.020 EUROVENT class DDCCDDD Prated, c (7) kw SEER (7) (8) 4.10 4.12 4.11 4.11 4.12 4.11 4.10 Annual degree of utilization ηs (7) (9)% CONSUMER SIDE IN COOLING MODE Water flow rate (1) l / s 57.11 61.64 64.56 69.97 73.16 76.27 78.86 Pressure loss (1) kpa 43.5 50.7 42.1 49.5 38.2 41.5 47.6 Number of compressors N Number of refrigeration circuits N Refrigerant charge kg Sound pressure (3) db (a) Sound power (4) (5) db (a) A (6) mm B (6 ) mm H (6) mm Operating weight (6) kg

16 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 289 to 1710 kw. 2 values ​​according to the EN standard: Average sound pressure level at a distance of 10 m, for devices outdoors on a reflective surface; Non-binding value determined from the sound power. 4 Sound power, measured according to the ISO 9614 standard. 5 Sound power in cooling mode, outside. 6 Device with standard configuration and design, without optional accessories. 7 Nominal cooling capacity for cooling operation [REGULATION (EU) 2016/2281] 8 Annual coefficient of performance in cooling operation 9 annual efficiency factor The devices specified in this document contain fluorinated greenhouse gases R513A [GWP]. EUROVENT-certified dates 16/17

17 16/17 R R513A ENERGY CLASS COOLING SCREW VPF VAR. PRIM. FLOW SHELL & TUBES AXIAL FX-G05 / CA Power supply V / ph / Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Cooling capacity (1) kw Total power consumption (1) kw 353.4 390.4 406.9 431.5 477.7 504.8 EER (1) kw / kw 3.107 3.015 3.038 3.110 3.056 3.013 ESEER (1) kw / kw 4.340 4.310 4.330 4.270 4.290 4,300 ONLY (EN14511 VALUE) cooling capacity (1) (2) kw EER (1) (2) kw / kw 3.060 2.980 3.000 3.070 3.030 2.980 ESEER (1) (2) kw / kw 4.160 4.160 4.160 4.120 4.160 4.160 EUROVENT class BBBBBB Prated, c (7) kw SEER (7) (8) 4.25 4.24 4.25 4.25 4.25 4.27 Annual degree of utilization ηs (7) (9)% CONSUMER SIDE IN COOLING MODE Water volume flow (1) l / s 52.53 56.31 59.13 64.17 69.81 72.73 Pressure loss (1) kpa 50.1 42.3 46.7 41.6 34.7 37.7 Number of compressors N Number of refrigeration circuits N Refrigerant charge kg Sound pressure (3) db (a) Sound power (4) (5) db (a) A (6) mm B (6) mm H (6) mm Operating weight (6) kg

18 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 289 to 1710 kw. 2 values ​​according to the EN standard: Average sound pressure level at a distance of 10 m, for devices outdoors on a reflective surface; Non-binding value determined from the sound power. 4 Sound power, measured according to the ISO 9614 standard. 5 Sound power in cooling mode, outside. 6 Device with standard configuration and design, without optional accessories. 7 Nominal cooling capacity for cooling operation [REGULATION (EU) 2016/2281] 8 Annual coefficient of performance in cooling operation 9 s annual energy efficiency The devices specified in this document contain fluorinated greenhouse gases R513A [GWP]. EUROVENT certified dates 18/19

19 18/19 R R513A ENERGY CLASS COOLING SCREW VPF VAR. PRIM. FLOW SHELL & TUBES AXIAL FX-G05 / SL-CA Power supply V / ph / Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Cooling capacity (1) kw Total power consumption (1) kw 347.6 384.6 401.4 426.7 479.4 EER (1) kw / kw 3.124 3.024 3.037 3.070 3.008 ESEER (1) kw / kw 4.330 4.310 4.330 4.280 4.280 ONLY (EN14511 VALUE) cooling capacity ( 1) (2) kw EER (1) (2) kw / kw 3.080 2.990 3.000 3.040 2.980 ESEER (1) (2) kw / kw 4.150 4.160 4.160 4.130 4.150 EUROVENT class BBBBB Prated, c (7) kw SEER (7 ) (8) 4.25 4.26 4.26 4.25 4.25 Annual efficiency ηs (7) (9)% CONSUMER SIDE IN COOLING OPERATION Water flow rate (1) l / s 51.94 55.63 58.31 62.64 68.95 Pressure loss (1) kpa 48.9 41.3 45.4 39.7 33.9 Number of compressors N Number of refrigeration circuits N Refrigerant charge kg Sound pressure (3) db (a) Sound power (4) (5) db (a) A (6) mm B (6) mm H (6) mm Operating weight (6) kg

20 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS FX-G Chiller, air-cooled, for outdoor installation, from 289 to 1710 kw. 2 values ​​according to the EN standard: Average sound pressure level at a distance of 10 m, for devices outdoors on a reflective surface; Non-binding value determined from the sound power. 4 Sound power, measured according to the ISO 9614 standard. 5 Sound power in cooling mode, outside. 6 Device with standard configuration and design, without optional accessories. 7 Nominal cooling capacity for cooling operation [REGULATION (EU) 2016/2281] 8 Annual coefficient of performance in cooling operation 9 annual efficiency factor The devices specified in this document contain fluorinated greenhouse gases R513A [GWP]. EUROVENT-certified dates 20/21

21 20/21 R R513A ENERGY CLASS COOLING SCREW VPF VAR. PRIM.

22 COMFORT AIR-COOLED CHILLERS WITH SCREW COMPRESSORS MORE THAN 1000 PROJECTS ALL OVER THE WORLD Howard Smith Wharves Brisbane, Australia, 2018 Mixed-use project Plant type: water-based system Cooling capacity: 1200 kw Devices used: 2x FX / CA cold water sets with screw compressors, Brookvale, Australia and high efficiency Brookvale , 2017 supermarket Plant type: water-based system Cooling capacity: 466 kw Devices used: 1x FX / K chiller with screw compressor Gabbana Windhof, Luxembourg, 2017 Office building Plant type: water-based system Cooling capacity: 386 kw Devices used: 1x FX-FC-HFO screw compressor, Free -Cooling water chiller with HFO refrigerant 22/23

23 22/23 Every project is characterized by different usage, location and system requirements. Thanks to the unique experience and know-how of Climaveneta, they all have the highest efficiency, lowest noise emissions and absolute reliability in common. Kernot Hall LaTrobe Victoria, Australia, 2018 Public facilities Plant type: water-based system Cooling capacity: 582 kw Devices used: 1x FX / K chiller with screw compressor FICO Eataly World Bologna, Italy, 2017 Food processing Plant type: water-based system Cooling capacity: 6324 kw Devices used: 2x highly efficient water chiller of type TECS2 SL CA with oil-free compressors, 2x highly efficient water chiller of type FOCS2 CA with screw compressors, 1x FX water chiller with screw compressor De Bijenkorf Amsterdam Amsterdam, Netherlands, 2018 Retail system type: water-based system Cooling capacity: 415 kw Devices used: 1x FX- HFO chiller with screw compressor and HFO refrigerant

24 DE-00098_CV